Model P522 Signal Processor

SIGNAL PROCESSOR FOR FLAME MONITOR SYSTEM

Model P522 Signal Processor for flame monitoring system

GENERAL DESCRIPTION

The IRIS Model P522 is a state of the art flame signal processor. It is designed to be used with the IRIS S5xx, S55x and S55xB series of  Viewing Heads.

The IRIS Model P522 shares the same electrical specifications as the IRIS Model P520, however, it is a panel mounted device, whereas the Model P520 is rack mounted.

Removable wiring connectors are provided to facilitate installation, and provide ease of removal of the unit if required.

In addition to the four LED's on the front panel, a digital readout and bar graph provide constant and concise information on the  system status.

The front panel also provides a number of controls for setting up and operation of this microprocessor based flame monitoring signal processor.

MAIN FEATURES: MODEL P522
 
Analog bar graph flame signal display
4-Digit digital flame signal display
Fail-safe self-checking
Digital set points for Flame On and Flame Off
Adjustable Flame Out time delay
Adjustable Flame On time delay
Separate analog and digital signal processors
0-20mA or 4-20mA current driven output for an analog remote meter
Two complete sets of set points, gain settings and time delays that can be programmed locally or remotely and can be selected remotely
Viewing head switching relay for igniter/main burner
Serial communication capability using RS-422 or RS-232 with a host computer for data acquisition and complete remote programming
Self-checking relay contacts available for DCS
Easy installation and rear mounted wiring terminals
Operates on 24VDC power or 24VDC backup
SETUP AND OPERATION DEMO
  Click to View an Online Demo
View an on-line demo of the operation of the P522 in Streaming Flash format.
This Demo runs in a separate window in your browser
.
You may need to install the Flash plug-in if it is not already installed.

 
 
       
 

Click to Download the PowerPoint demo
This is a high resolution full screen demo that runs on your PC. It is suitable for projection or large screen monitors. The file size is 4Mb.
Choose SAVE to save the file to your hard drive. You must have the PowerPoint 2003 viewer installed on your PC to view this demo.
 
Download PowerPoint Viewer 2003

 
APPLICATIONS:

Discriminates Between All Types Of Burner Flames

  • Power Utility Boilers
  • Industrial Power Boilers

Discriminates Between Main Flame And Unwanted Background

  • Liquor Recovery Boilers
  • Grate Fired Boilers
  • Lime Kilns

In the Process Industries

  • Claus Reactors (H2S)
  • Duct Burners
  • Hydrogen Burners
LOCAL OR REMOTE PROGRAMMING CAPABILITY:
It is possible, for example, to program the FLAME ON and FLAME OFF set-points locally (from the front panel) or remotely (from a host computer) using FlameTools 95/NT software.
The P522 communicates with the remote computer through its RS-422 to RS-232 converter at either 4800 or 9600 baud selectable at the P522 processor front panel.
APPROVALS:
The IRIS Model P522 Signal Processor has FM (Factory Mutual) approval and CSA (Canadian Standards Association) certification.
SPECIFICATIONS: MODEL P522
ELECTRICAL P522 DC Input Power 22-26 VDC, 130mA plus 100 mA for each Viewing Head
P522 AC Input Power 85-264 VAC, 47-440 Hz, 0.3A Maximum
Battery Power 22-24 VDC, 130mA plus 100 mA for each Viewing Head
Power to Viewing Head +26 VDC, fused @ 0.25A
 
ENVIRONMENTAL Ambient Temperature 0oC to 50oC (32oF to 122oF)
 
CABLE Signal Processor to V.H. 4 conductor, #18AWG one wire with braided shield (Iris C328)
 
OUTPUTS Flame Relay 2 form C contacts
Self-Checking Relay 1 form C contacts
Relay Contact Ratings 5A at 30VDC, 125VAC and 277VAC
Analog Flame Signal 0 to 20 mA or 4 to 20 mA output for remote meters
360 ohm maximum resistance
Power to Viewing Head +26 VDC, Self Resetting fused, 0.25A
+14.3 VDC Pulsing 0.2 Sec ON, 0.8 Sec OFF
 
INPUTS Channel Select (Isolated Input Req. 2 wires) Vin 7.5-30 VDC range (Input R=3900 Ohms)
26 VDC, 6.4mA
10 VDC, 2.3mA
Flame Signal from Viewing Head Vin 7.5-30 VDC range (Input R=3900 Ohms)
13.6 VDC, 3.2mA
 
SERIAL COMMUNICATION RS-422 (Differential)
4800 or 9600 baud
Input/Output circuits photo coupler isolated from P520 power supplies and ground.
Baud rate selectable from front panel of P520
 
 
Send mail to flame@iris-systems.com with questions or comments about this web site.
 Copyright © 2006 Iris Systems Inc. 7583 Vantage Place, Delta BC. V4G 1A5
 Last Updated on 02/14/2006
 
 
 IRIS Signal Processors, Flame Monitors, Viewing Heads and Flame Detectors are made in the USA