SIGNAL PROCESSOR FOR FLAME MONITOR SYSTEM
|
|
 |
GENERAL DESCRIPTION
The IRIS Model P522 is a state of the art flame signal processor. It is
designed to be used with the IRIS S5xx, S55x and S55xB series of Viewing
Heads.
The IRIS Model P522 shares the same electrical specifications as the
IRIS Model P520, however, it is a panel mounted device, whereas the Model
P520 is rack mounted.
Removable wiring connectors are provided to facilitate installation, and
provide ease of removal of the unit if required.
In addition to the four LED's on the front panel, a digital readout and
bar graph provide constant and concise information on the system
status.
The front panel also provides a number of controls for setting up and
operation of this microprocessor based flame monitoring signal processor.
|
|
MAIN FEATURES: MODEL P522 |
| |
 |
Analog bar graph flame signal display |
 |
4-Digit digital flame signal display |
 |
Fail-safe self-checking |
 |
Digital set points for Flame On and Flame Off |
 |
Adjustable Flame Out time delay |
 |
Adjustable Flame On time delay |
 |
Separate analog and digital signal processors |
 |
0-20mA or 4-20mA current driven output for an analog remote meter |
 |
Two complete sets of set points, gain settings and time delays that can be programmed
locally or remotely and can be selected remotely |
 |
Viewing head switching relay for igniter/main burner |
 |
Serial communication capability using RS-422 or RS-232 with a host computer for data
acquisition and complete remote programming |
 |
Self-checking relay contacts available for DCS |
 |
Easy installation and rear mounted wiring terminals |
 |
Operates on 24VDC power or 24VDC backup |
|
|
SETUP AND OPERATION DEMO |
| |
Click to View an Online Demo
View an on-line demo of the operation of the
P522 in Streaming Flash format.
This Demo runs in a separate
window in your browser.
You may need to install the Flash plug-in if it is not already
installed.
|
|
 |
| |
|
|
|
| |
Click to Download
the PowerPoint demo
This is a high resolution full screen demo
that runs on your PC. It is suitable for projection or large screen monitors. The file size is
4Mb.
Choose SAVE to save the file to your hard drive.
You must have the PowerPoint 2003 viewer installed on your PC to view this
demo.
Download PowerPoint Viewer 2003 |
|
 |
|
APPLICATIONS: |
Discriminates Between All Types Of Burner Flames
- Power Utility Boilers
- Industrial Power Boilers
Discriminates Between Main Flame And Unwanted Background
- Liquor Recovery Boilers
- Grate Fired Boilers
- Lime Kilns
In the Process Industries
- Claus Reactors (H2S)
- Duct Burners
- Hydrogen Burners
|
|
LOCAL OR REMOTE PROGRAMMING
CAPABILITY: |
It is possible, for example, to program the
FLAME ON and FLAME OFF set-points locally (from the front panel) or remotely
(from a host computer) using FlameTools 95/NT software.
The P522
communicates with the remote computer through its RS-422 to RS-232 converter
at either 4800 or 9600 baud selectable at the P522 processor front panel. |
| APPROVALS: |
| The IRIS Model P522 Signal Processor has FM
(Factory Mutual) approval and CSA (Canadian Standards Association)
certification. |
| SPECIFICATIONS: MODEL P522 |
|
ELECTRICAL |
P522 DC Input Power |
22-26 VDC, 130mA plus 100 mA for each
Viewing Head |
| P522 AC Input Power |
85-264 VAC, 47-440 Hz, 0.3A Maximum |
| Battery Power |
22-24 VDC, 130mA plus 100 mA for each
Viewing Head |
| Power to Viewing Head |
+26 VDC, fused @ 0.25A |
| |
| ENVIRONMENTAL |
Ambient Temperature |
0oC to 50oC (32oF to 122oF)
|
| |
| CABLE |
Signal Processor to V.H. |
4 conductor, #18AWG one wire with braided shield
(Iris C328) |
| |
|
OUTPUTS |
Flame Relay |
2 form C contacts |
| Self-Checking Relay |
1 form C contacts |
| Relay Contact Ratings |
5A at 30VDC, 125VAC and 277VAC |
| Analog Flame Signal |
0 to 20 mA or 4 to 20 mA output for remote meters
360 ohm maximum resistance |
| Power to Viewing Head |
+26 VDC, Self Resetting fused, 0.25A
+14.3 VDC Pulsing 0.2 Sec ON, 0.8 Sec OFF |
| |
|
INPUTS |
Channel Select (Isolated Input Req. 2 wires) |
Vin 7.5-30 VDC range (Input R=3900 Ohms)
26 VDC, 6.4mA
10 VDC, 2.3mA |
| Flame Signal from Viewing Head |
Vin 7.5-30 VDC range (Input R=3900 Ohms)
13.6 VDC, 3.2mA |
| |
| SERIAL COMMUNICATION |
RS-422 (Differential)
4800 or 9600 baud |
Input/Output circuits photo coupler isolated from P520 power supplies and ground.
Baud rate selectable from front panel of P520 |
|