Model P531/P532UI signal processor and user interface

SIGNAL PROCESSOR FOR FLAME MONITOR SYSTEM

Model P531 flame monitor signal processor

GENERAL DESCRIPTION:

The IRIS Model P531 Signal Processor provides a lower cost alternative to the Model P532, as it is basically the same processor without the integrated front panel user interface.

Combined with the IRIS P532UI, all the functions of the P532 can be achieved. In addition, the Model P531can be programmed via software, using your PDA (Personal Digital Assistant) and the optional interface cable.

As with the Model P532, the P531 uses a Dual Processor system to provide the ability to monitor up to three viewing heads simultaneously. With Automatic Viewing Head detection, the P531 is also capable of monitoring UV and IR separately. Each channel can be associated with Two sets of configuration data: Primary, or Alternate.


The Model P531 is compatible with both RS422 and Modbus protocols. It has an automatic set up functionality whereby each channel can be configured automatically in one of three ways: Auto Fit, Auto Sequence, or Auto Filter.

Model P531 flame monitor User Interface

Model P531 shown with programming option

IRIS Model P532UI User Interface

IRIS Model P531 shown with optional interface cable and PDA

MAIN FEATURES: MODEL P531
 
  • Ability to monitor 3 Viewing Heads simultaneously
  • Dual processor system
  • Ability to monitor UV and IR separately from one S550x view head
  • Seven front panel LED status indicators
  • Automatic viewing head detection
  • Each channel and viewing head can be associated with two sets of configuration data:

Primary is the normal viewing head configuration

Alternate is a set of alternate settings that can be activated by applying a voltage across the alternate select pins for each specific channel or writing configuration to Modbus register.

  • Automatic set up functionality where each channel can be configured automatically in one of three ways.

Auto Fit: The flame is monitored and the gain is adjusted to produce an optimal count of between 1100 and 1300. The flame on will then be set at 800 and flame off will be set to 600.

Auto Sequence: The gain will first be adjusted as in the Auto Fit routine and then the flame on and flame off settings will be adjusted. (This requires turning off the flame).

Auto Filter: Used for definitive infrared calibration. The sequence procedure (above) is performed on each of the 8 filter settings. The best-differentiated filter is chosen and configured for gain, flame on and flame off settings.

  • Viewing head error detection with viewing head lockout capabilities (requiring physical acknowledgment).
  • A P522 emulation mode can be achieved by installing a jumper between the two P522 pins.
  • Changing viewing head types (while operating) will cause the unit to go into lockout mode. (This is a safety feature).
  • Compatible with RS422 and Modbus protocol.
  • Field upgradeable with firmware download capabilities.
  • 702 / 802 IR and the 706 / 806 UV viewing heads can be connected to Viewing Head #3.
  • S552 IR and S556 UV together with the S550 that utilizes both UV and IR sensors can be connected to Viewing Head #2 and #3.

WITH P532UI ATTACHED:

  • Large bright scrolling 3-color dot matrix displays:
    • Red indication for IR
    • Green indication for UV
    • Orange indication for mixture of IR and UV

WITH PDA ATTACHED VIA INTERFACE CABLES:

  • All the functionalities of the Model P532 ( or P531 with P532UI attached) are available via software on your PDA.
SETUP AND OPERATION DEMO
  Click to View an Online Demo
View an on-line demo of the operation of the P531/P532 in Streaming Flash format. This Demo runs in a separate window in your browser.
You may need to install the Flash plug-in if it is not already installed.

 
 
       
 

Click to Download the PowerPoint demo
This is a high resolution full screen demo that runs on your PC. It is suitable for projection or large screen monitors. The file size is 8Mb.
Choose SAVE to save the file to your hard drive. You must have the PowerPoint 2003 viewer installed on your PC to view this demo.

Download PowerPoint Viewer 2003

 
 
APPLICATIONS:

Discriminates Between All Types Of Burner Flames

  • Power Utility Boilers
  • Industrial Power Boilers

Discriminates Between Main Flame And Unwanted Background

  • Liquor Recovery Boilers
  • Grate Fired Boilers
  • Lime Kilns

In the Process Industries

  • Claus Reactors (H2S)
  • Duct Burners
  • Hydrogen Burners
APPROVALS
The IRIS Model P532 Signal Processor has FM (Factory Mutual) approval and CSA (Canadian Standards Association) certification.
SPECIFICATIONS: MODEL P531  WITH P532UI
ELECTRICAL Input Power - AC Version Main Power:  85 VAC to 264 VAC, 47-63 Hz
Battery: 24 VDC (voltage above 24 volt will be the power source)
Input Power - DC Version Main Power: 24 VDC
Battery: 24 VDC (power source is taken from the highest voltage)
Power (DC unit tested at 100ms. sampling time) 13.2 Watts max. Average (including 3 view heads)
16.2 Watts max. Peak (including 3 heads in normal operation
ENVIRONMENTAL Ambient Temperature -40° F - 140° F (-40° C to 60° C (FM) or 32° F - 125° F (0° C to 52° C) (CSA)
Humidity Non-condensing Maximum 80% for temperatures below 88° F (31° C) Decreasing to 50% maximum at 104° F (40° C) and above
Vibration +1 g at 10 to 150 Hz
OUTPUTS Flame Relay 3 channels of 2 Form C Contacts (DPDT) Contact Rating:
5A at 32 VDC and at 250 VAC
Self-Check Relay 3 channels of 1 Form C Contact (SPDT)
Alarm Relays 3 channels of 1 Form A Contact (SPST-N.O.) Contact Rating: 2 A at maximum 250 VDC or 230 VAC
Analog Flame Signal 0 ? 20 mA or 4 ? 20 mA
1000 ohm maximum resistance
Power To Viewing heads 100 mA (maximum average)
24 VDC (rated)
Current limited to 200 mA
24v output 24-volt output 50 mA
For Instrumentation use only
Provided for use with Isolated Select
INPUTS Isolated Select 7.5 ? 30 VDC
Input Resistance 3900 ohm
Aux Mode Connect to ground only
(WARNING: do not apply Power)
Sources 1 mA at 5 VDC
Viewing head Signal (for 55x and 70x view heads) 26-Volt P-P Maximum
1 MA
SERIAL COMMUNICATIONS
RS-422 / 4 wire (two twisted pair)
Baud 38400, 19200, 9600 or 4800
Parity None, Even or Odd
Protocol Modbus (RTU)
FLAME
(No large Maximum flame signal will cause lost flame indication)
Maximum flame detector response time 5 seconds
Minimum flame detector self-checking rate 1 second
Maximum flame failure response time 2 to 4 seconds (adjustable)
Signal for presence of flame Flame on set point (adjustable)
Signal for absence of flame Flame off set point (adjustable)
COMPATIBILITY Viewing head #3 S702, S706, S802 or S806 (including -PH and -HF versions)
Viewing head #1 or #2 S550x, S552x, S556x (including -PF versions)
FUSES Internal self-resetting fuse +24 PWR DC input voltage supply (DC units only)
Internal self-resetting fuse +24 BATT Battery input voltage supply
CABLE Processor to viewing head Connection from the Signal processor to the view heads shall use approved cable:
Cable can be Instrument Tray cable with CIC C22.2 No. 239 certification such as IRIS C-330
Or must be run inside of Conduit (with properly sealed ends).
 
 