ELECTRICAL |
Input Power -
AC Version |
Main Power:
85 VAC to 264 VAC, 47-63 Hz
Battery: 24 VDC (voltage above 24 volt will be the power source)
|
| Input Power -
DC Version |
Main Power:
24 VDC
Battery: 24 VDC (power source is taken from the highest voltage)
|
| Power |
(DC unit tested at 100ms.
sampling time) |
13.2 Watts
max. Average (including 3 view heads)
16.2 Watts max. Peak (including 3 heads in normal operation |
|
|
ENVIRONMENTAL |
Ambient Temperature |
-40° F - 140°
F (-40° C to 60° C (FM) or 32° F - 125° F (0° C to 52° C) (CSA) |
| Humidity |
Non-condensing Maximum 80% for temperatures below 88° F (31° C)
Decreasing to 50% maximum at 104° F (40° C) and above |
| Vibration |
+1 g at 10 to
150 Hz |
|
|
OUTPUTS |
Flame Relay |
3 channels of 2 Form C
Contacts (DPDT) |
Contact
Rating:
5A at 32 VDC and at 250 VAC |
| Self-Check
Relay |
3 channels of 1 Form C
Contact (SPDT) |
| Alarm Relays |
3 channels of 1 Form A
Contact (SPST-N.O.) |
Contact Rating: 2 A at
maximum 250 VDC or 230 VAC |
| Analog Flame
Signal |
0 ? 20 mA or
4 ? 20 mA
1000 ohm maximum resistance |
| Power To
Viewing heads |
100 mA
(maximum average)
24 VDC (rated)
Current limited to 200 mA |
| 24v output
|
24-volt
output 50 mA
For Instrumentation use only
Provided for use with Isolated Select |
|
|
INPUTS |
Isolated
Select |
7.5 ? 30 VDC
Input Resistance 3900 ohm |
| Aux Mode
|
Connect to
ground only
(WARNING: do not apply Power)
Sources 1 mA at 5 VDC |
| Viewing head
Signal (for 55x and 70x view heads) |
26-Volt P-P
Maximum
1 MA |
|
SERIAL COMMUNICATIONS
RS-422 / 4 wire (two twisted pair) |
Baud |
38400, 19200,
9600 or 4800 |
| Parity |
None, Even or
Odd |
| Protocol |
Modbus (RTU) |
|
FLAME
(No large Maximum flame signal will cause lost flame indication) |
Maximum flame
detector response time |
5 seconds |
| Minimum flame
detector self-checking rate |
1 second |
| Maximum flame
failure response time |
2 to 4
seconds (adjustable) |
| Signal for
presence of flame |
Flame on set
point (adjustable) |
| Signal for
absence of flame |
Flame off set
point (adjustable) |
|
|
COMPATIBILITY |
Viewing head
#3 |
S702, S706,
S802 or S806 (including -PH and -HF versions) |
| Viewing head
#1 or #2 |
S550x, S552x,
S556x (including -PF versions) |
|
|
FUSES |
Internal
self-resetting fuse |
+24 PWR DC
input voltage supply (DC units only) |
| Internal
self-resetting fuse |
+24 BATT
Battery input voltage supply |
|
|
CABLE |
Processor to
viewing head |
Connection
from the Signal processor to the view heads shall use approved
cable:
Cable can be Instrument Tray cable with CIC C22.2 No. 239
certification such as IRIS C-330
Or must be run inside of Conduit (with properly sealed ends). |